Case: T08FR00612
Case Details
Entered Date:
03/04/2008
Applicant:
MACHADO JOSEPH JAMES 1/3 & MACHADO
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR00612
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC- Remove storage from obstructing the sprinkler head located in the wald-in frige. |
03/04/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Replace all missing ceiling tiles. |
03/04/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.3.3- Automatic sprinklers shall be installed in or under covered kiosks, displays, booths of equipment that exceeds 4 feet in width. #1. An automatic sprinkler system head shall be installed inside the walk-in freezer. |
03/04/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC- All portable fire extinguishers shall be mounted on the wall with a hanger or bracket. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00612
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violation have been corrected. |