Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/04/2008

Applicant:

MACHADO JOSEPH JAMES 1/3 & MACHADO

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T08FR00610
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
03/04/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Service and tag the automatic sprinkler system or provide documentation of the current inspection.
03/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Remove the locking bar hardware from the back door.
03/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3- Post a sign stating,"THIS DOOR TO REMAIN UNLOCKEDWHEN BUILDING IS OCCUPIED." The sign shall be posted on the inside of the entrance door.
03/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the emergency lighting unit located on the south wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00610
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/27/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.