Case: T08FR00518
Case Details
Entered Date:
02/22/2008
Applicant:
CIRCLE PLAZA ASSOCIATES LLC 50% &
Description:
FULL FIRE INSPECTION.
Outstanding Inspections
Case Number: T08FR00518
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Violation | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ____ Label RISER ROOM. |
| 02/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____ Service and tag extinguishers. |
| 02/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. ____ Hang fire extinguishers in an unobstructed and unobscured location. |
| 02/22/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ____ Remove slide bolt from rear exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00518
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | INSP - FULL | JVINCENT | Approved | FULL FIRE INSPECTION. |