Case: T08FR00513
Case Details
Entered Date:
02/21/2008
Applicant:
535 WILMOT INVESTORS LP
Description:
Full inspection done 2/21/2008; "B" occupancy; 2 story; COBRA preplan being done. Sprinklered- current, C of O in file. Contact: Sergio Centeno 631-0083; Owned and Managed by Schomac Group 577-9898 Cindy Moos.
Outstanding Inspections
Case Number: T08FR00513
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2008 | INSP - FULL | BCOBB | Violation | Please correct the following Tucson Fire Code [IFC 2006 with modifications] violations: Note: 1. A record of the sprinkler system inspections shall be made available upon re-inspection. [Should be kept on premises] 2. Place a "Roof Access" sign on 2nd floor door leading to roof ladder. |
02/21/2008 | VIOL - FIRE RESIST.RATED CONST | BCOBB | Violation | Missing or moved ceiling tiles: IFC2006 [TFC with modifications] / 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing ceiling tiles. Communications rooms- 1st and 2nd floors. |
02/21/2008 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | Escutcheons and sprinkler heads: IFC2006 [TFC with modifications] / 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Have escutcheons fixed, and sprinkler heads lowered where necessary. [2nd floor conference room, 1sr floor men's room] Re-inspection date scheduled on or after March 7, 2008. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |