Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/12/2008

Applicant:

TUCSON ASSN FOR THE BLIND

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR00415
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
02/12/2008 VIOL - PRECAUTION AGAINST FIRE JVINCENT Violation 313.1 General. Fueled equipment, including but not limited to motorcycles, mopeds, lawn-care equipment and portable cooking equipment, shall not be stored, operated or repaired within a building. ___ Remove fueled equipment from North side unit.
02/12/2008 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Violation 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ___ Install cover plates on all outlets and light switches in computer room.
02/12/2008 VIOL - FIRE RESIST.RATED CONST JVINCENT Violation 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. ___ Replace all missing ceiling tiles. Room B, computer room and administration room.
02/12/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ___ All extinguishers need to be serviced and tagged.
02/12/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 907.20 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with this section and Chapter 10 of NFPA 72. ___ Fire alarm needs testing in all three buildings.
02/12/2008 VIOL - MEANS OF EGRESS JVINCENT Violation 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate... ___ Repair all emergency lighting units.
02/12/2008 VIOL - MEANS OF EGRESS JVINCENT Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, ___ Place a sign/sticker above main door in North side unit.
02/12/2008 VIOL - MEANS OF EGRESS JVINCENT Violation 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ___ Repair exit sign in North hallway, main building.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00415
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/26/2008 INSP - FULL JVINCENT Approved ALL VIOLATIONS CORRECTED. 02/26/2008.