Case: T08FR00223
Case Details
Entered Date:
01/22/2008
Applicant:
SEASONS PARTNERS LLC
Description:
Full Inspecton.
Outstanding Inspections
Case Number: T08FR00223
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 506.1.1 An approved fire department lock shall be provided for the emergency gate control box. |
| 01/22/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4 Remove storage from the riser and electrical rooms. |
| 01/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 All electric meter breaker switches and electrical panels shall be locked shut to prevent shock or fire hazard. |
| 01/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 607.1 Repair all broken elevators and replace all missing elevator buttons. |
| 01/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag all sprinkler systems. #2.Replace all missing standpipe connection caps. #3.Remove the tape from obstructing the sprinkler head in building 1, 2nd floor north side patio. |
| 01/22/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Remove the double keyed lock from the east door in the gym. NOTE: replace it with a thumb-turn lock. |
| 01/22/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 Post, THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIEED, on the inside of the west exit door in the gym. |
| 01/22/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 All emergency lighting units shall be tested and repaired or replaced where defective. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00223
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |