Case: T08FR00216
Case Details
Entered Date:
01/22/2008
Applicant:
RODRIGUEZ FAMILY FP LLC 51% &
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00216
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 The building address numbers shall be moved so they are not obstructed by tree's. |
| 01/22/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1 Post a sign on the door of the sprinkler system riser room stating RISER ROOM. |
| 01/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag all portable fire extinguishing systems. |
| 01/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood systems. |
| 01/22/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 Post THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED on the main entrance/exit door. |
| 01/22/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.4 Repair the brocken exit sign located in the kitchen. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00216
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |