Case: T08FR00099
Case Details
Entered Date:
01/10/2008
Applicant:
N/A
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00099
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 504.2 Post the stated sign on the exterior side of the door in the maintenance cage. NOTE: Not Needed. Door not blocked. |
| 01/10/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service, test and tag the fire alarm system or provide documentation of such work. #2.Chain and lock the automatic sprinkler control valves in the open position. #3.The two fire blanket cabinets located in the warehouse should be mounted lower for easy acess in case of fire or emergency. |
| 01/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 Post the stated sign on the inside of the main entrance door. |
| 01/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 The exit sign located in the office above the north exit door shall be illuminated. |
| 01/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 #1.Repair the emergency lighting unit located on the wall south of the mail boxes in the office. #2.Repair the emergency lighting unit located on the wall by the shipping computer area. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00099
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |