Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/09/2008

Applicant:

SOUTHWEST COMMODITIES WAREHOUSE INC

Description:

Full Inspection

Outstanding Inspections

Case Number: T08FR00087
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/09/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Portable fire extinguisher at west side of freezer room shall be inspected.
01/09/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Sprinkler system shall be inspected annually.
01/09/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 Exit signs shall be installed in freezer room in order to use room as mercantile.
01/09/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.3 Exit signs throughout shall be maintained.
01/09/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 Emergency illumination lights shall be maintained.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00087
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/23/2008 INSP - FULL TKNAPP Approved