Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/07/2008

Applicant:

N/A

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00071
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/07/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Open space in the electrical panel located by the office shall be properly covered with electrical blanks.
01/07/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the automatic sprinkler system.
01/07/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood and cooking equipment.
01/07/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 The red portable fire extinguisher located in the kitchen shall be mounted no higher than 5 feet from it's top.
01/07/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 The southe exit sign shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00071
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/05/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.