Case: T08FR00071
Case Details
Entered Date:
01/07/2008
Applicant:
N/A
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00071
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 Open space in the electrical panel located by the office shall be properly covered with electrical blanks. |
01/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the automatic sprinkler system. |
01/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood and cooking equipment. |
01/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 The red portable fire extinguisher located in the kitchen shall be mounted no higher than 5 feet from it's top. |
01/07/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 The southe exit sign shall be illuminated. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00071
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |