Case: T08FR00069
Case Details
Entered Date:
01/07/2008
Applicant:
N/A
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00069
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 506.2 The fire department lock box located by the entrance shall contain keys to gain necessary access as required by the fire code official. |
| 01/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag all portable fire extinguishers. #2.Service and tag the automatic sprinkler system. |
| 01/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6 The portable fire extinguisher located by the photo center shall not be obstructed from view. |
| 01/07/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 #1.Repair the emergency lighting unit located in the locker hallway. #2.All emergency lighting units shall be tested and repaired where defective. |
| 01/07/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 The compressed gas cylinder located in the electrical room shall be secured to a fixed object with one or more restraints. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00069
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |