Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/03/2008

Applicant:

N/A

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00025
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/03/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Replace the missing cover to the electrical junction box located in the kitchen by the southwest door.
01/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service, tag and mount the silver class K portable fire extinguisher. #2.Service, test and tag the hood extinguishing system.
01/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood system and cooking equipment.
01/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the broken panic hardware from the door in the kitchen.
01/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 The exit sign located in the dinning area shall be illuminated at all times.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00025
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/11/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.