Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/03/2008

Applicant:

N/A

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00022
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/03/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 #1.Remove the cube adapter located behind the front counter. #2.Remove the cube adapter located in the office.
01/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service, tag and mount the portable fire extinguisher located behind the counter.
01/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the double keyed lock from the south door. Note: Replace the double keyed lock with a thumb-turn lock.
01/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Remove the surface bolt from the south door
01/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Repair the emergency lighting unit located by the northeast door.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00022
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/23/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.