Case: T08FR00022
Case Details
Entered Date:
01/03/2008
Applicant:
N/A
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00022
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4 #1.Remove the cube adapter located behind the front counter. #2.Remove the cube adapter located in the office. |
01/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service, tag and mount the portable fire extinguisher located behind the counter. |
01/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Remove the double keyed lock from the south door. Note: Replace the double keyed lock with a thumb-turn lock. |
01/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4 Remove the surface bolt from the south door |
01/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Repair the emergency lighting unit located by the northeast door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00022
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |