Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/28/2007

Applicant:

CAMPBELL AVENUE SHOPPING CENTER LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR02641
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
12/28/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove all combustible material storage from the water heater corner so that ignition cannot occur.
12/28/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 18 inches of clearance shall be maintained below sprinkler heads located in the back room.
12/28/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the extension cord located on the west side of the sales area. { Used to power the window signs.} NOTE: Replace the extension cord with a fused power strip.
12/28/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Repair the hole in the wall located by the south egress door.
12/28/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service, tag and mount the portable fire extinguisher located by the back door.
12/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the chain and padlock from the south egress door.
12/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Remove one of the two locks on the main entrance/exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02641
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/28/2007 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: