Case: T07FR02592
Case Details
Entered Date:
12/26/2007
Applicant:
CAMPBELL AVENUE SHOPPING CENTER LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T07FR02592
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Replace all missing electrical outlet covers located in the back room. |
12/26/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.5 Remove the thumb-turn lock from the bottom of the exit/entrance door. |
12/26/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 The compressed gas cylinder shall be secured to a fixed object with one or more restraints. Located in the back office. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02592
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2007 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |