Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/26/2007

Applicant:

CAMPBELL AVENUE SHOPPING CENTER LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T07FR02591
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag the hood extinguishing system. #2.Service and tag the portable fire extinguisher. NOTE:Provide documentation if the work has already been completed.
12/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the double keyed lock from the north egress door located in the dinning area.
12/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 #1.Remove one of the two thumb-turn locks from the egress door located in the kitchen. #2.Remove the locking bar hardware from the egress door located in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02591
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/26/2007 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: