Case: T07FR02528
Case Details
Entered Date:
12/13/2007
Applicant:
LA PLAZA INVESTORS
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02528
Case Description: INSPECTION
Total Completed Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Approved | 2006 IFC 605.1 INSTALL A BLANK IN UNCOVERED SLOT IN ELECTRICAL PANEL |
| 03/06/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 2006 IFC 1008.1.9 ADJUST DOOR ON WEST SIDE SO IT OPENS FREELY AND WITH NO MORE THAN 15 LBS OF FORCE. |
| 03/06/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 2006 IFC 1008.1.8.4 REMOVE SLIDE BOLTS ON BREAK ROOM EXIT DOOR REMOVE SLIDE BOLTS ON OFFICE EXIT DOOR REMOVE SLIDE BOLTS ON EXIT DOOR BY RESTROOM |
| 03/06/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 2006 IFC 1008.1.8 REMOVE DOUBLE KEYED DEADBOLT ON BREAKROOM EXIT DOOR AND REPLACE WITH A THUMB TURN. TRMOVE DBL KEYED DEADBOLT ON EXIT DOOR BY THE OFFICE AND REPLACE WITH A THUMB TURN REMOVE DBL KEYED DEADBOLT ON EXIT DOOR BY REST ROOM AND REPLACE WITH A THUMB TURN |
| 03/06/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT ON WEST SIDE OF RESTAURANT REPAIR EMERGENCY LIGHT BY WAITRESS STATION |
| 03/06/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 2006 IFC 1027.3 REPAIR EXIOT SIGN IN WEST SIDE OF RESTAURANT REPAIR EXIT SIGN AT BREAK ROOM REPAIR EXIT SIGN BY OFFICE DOOR REMOVE PAPER OVER EXIT SIGN BY REST ROOMS |
| 03/06/2008 | INSP - FULL | MWAINWRI | Approved |