Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/10/2007

Applicant:

PRESSON MIDWAY LLC

Description:

Full inspection done 12/5/2007; "A2" occupancy; Jay Tolkoff- owner, 798-1200; C of O in process of name change; [same business]

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02507
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
12/10/2007 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Extinguishers not tagged / inspected: IFC2006 [TFC with modifications] / 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. Re-inspection date scheduled on or after Dec. 31, 2007. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain
12/10/2007 VIOL - FIRE RESIST.RATED CONST BCOBB Approved Missing or moved ceiling tiles: IFC2006 [TFC with modifications] / 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing ceiling tiles.
12/10/2007 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Multiplug adapters: IFC2006 [TFC with modifications] / 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ______Remove noncomplying devices.
12/10/2007 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Extension cords: IFC2006 [TFC with modifications] / 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved power strip.
12/10/2007 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code [IFC 2006 with modifications] violations: Note: The office area is not a public area, and does not effect exiting, and therefore is allowed to have a keyed lock.
02/28/2008 INSP - REINSPECTION BCOBB Approved All approved - closed.