ARIZONA BETA OF SIGMA PHI EPSILON
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02503
Case Description: INSPECTION
Total Completed Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | VIOL - MEANS OF EGRESS | BCORRALE | Approved | ____Exit sign out of service in emergency mode. (Dining room) 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.****Repair exit sign. |
| 12/07/2007 | VIOL - MEANS OF EGRESS | BCORRALE | Approved | ____Bicycles chained to exit stairwell handrails, also in exit path. (1st floor) 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. ****Remove bikes from stairway area, unblock exit access. |
| 12/07/2007 | VIOL - MEANS OF EGRESS | BCORRALE | Approved | ____Sprinkler test due, results shall be fowarded to T.F.D. ____Alarm test due, results shall be fowarded to T.F.D. ____Smoke detector missing cover. (2nd floor hall) ____Replace smoke detector. (Room 202) Painted over. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ****Replace ALL defective detectors. ****Submit copies of inspection reports to T.F.D. |
| 12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Approved | ____Switch blanks missing in electrical panel. ____Switch covers broken. (Dining room) ____Outlet covers missing. (T.V. room) 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. ****Replace ALL missing/damaged covers. |
| 12/07/2007 | VIOL - ADMINISTRATION | BCORRALE | Approved | ____Fireplace lacks a grate to contain wood, also chimney not cleaned. 110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. ****No fire shall occur in fireplace until grate is installed AND chimney is inspected by a licensed professional, per the mechanical code. |
| 12/07/2007 | INSP - FULL | BCORRALE | Approved | On 12-04-07, a fire prevention inspection was conducted at the Sigma Pi Epsilon fraternity house. Please correct the following Tucson Fire Code violations. All code references are from the 2006 International Fire Code, with modifications. |