Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR02469
Case Details
Entered Date:
12/05/2007
Applicant:
N/A
Description:
Full Inspection.
Outstanding Inspections
Case Number: T07FR02469
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Storage located in the electrical room shall not obstruct the electrical service equipment. |
12/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the automatic sprinkler system. |
12/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 All portable fire extinguishers shall be mounted. |
12/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 #1.Remove the locking bar and hardware from the exit doors located on the northeast side of the building. #2.Remove the locking bar and hardware from the exit doors located on the south side of the building. {In the processing area.} |
12/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 Post,"THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED" on the egress gate in the electrical area. |
12/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2 The northeast exit doors shall not be obstructed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02469
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Approved | TFC 315.3.1 Install an automatic sprinkler system to protect the electrical canopy, or remove all combustible storage from under the electrical canopy. |
12/05/2007 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |