Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/05/2007

Applicant:

N/A

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR02469
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/05/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Storage located in the electrical room shall not obstruct the electrical service equipment.
12/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the automatic sprinkler system.
12/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 All portable fire extinguishers shall be mounted.
12/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 #1.Remove the locking bar and hardware from the exit doors located on the northeast side of the building. #2.Remove the locking bar and hardware from the exit doors located on the south side of the building. {In the processing area.}
12/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 Post,"THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED" on the egress gate in the electrical area.
12/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 The northeast exit doors shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02469
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/05/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Approved TFC 315.3.1 Install an automatic sprinkler system to protect the electrical canopy, or remove all combustible storage from under the electrical canopy.
12/05/2007 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: