Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/30/2007

Applicant:

FUNG DAVID MICHAEL & LEUNG-FUNG WINNIE JT/RS 1/2

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02446
Case Description: INSPECTION
Total Completed Inspections - 9
End Date Description Inspector Results Comments
01/25/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 HAVE HEADS CHECKED FOR PROPER PLACEMENT OVER COOKING APPLIANCES
01/25/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.6.3 HAVE FILTERS CLEANED IN HOOD SYSTEM
01/25/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 HAVE SPRINKLER SYSTEM TESTED AND TAGGED HAVE HOOD SYSTEM TESTED AND TAGGED. HAVE FIRE EXTINGUISHER BEHIND FRONT COUNTER SEVICED AND TAGGED.
01/25/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.4 USE A POWER STRIP IN PLACE OF THE UNFUSED CUBE BY THE SECURITY MONITER IN KITCHEN AREA.
01/25/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.5 REMOVE EXTENSION CORD IN KITCHEN BY SECURITY MONITER WHCIH SUPPLIES POWER TO THE COMPUTERS IN THE OFFICE.
01/25/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8 REMOVE DOUBLE KEYED LOCK ON KITCHEN EXIT DOOR AND REPLACE WITH THUMB TURN.
01/25/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT IN DINING ROOM REPAIR EMERGENCY LIGHT IN KITCHEN
01/25/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 REPAIR EXIT SIGN AT FRONT EXIT REPAIR EXIT SIGN AT REAR DINING ROOM EXIT
01/25/2008 INSP - FULL MWAINWRI Approved