Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/30/2007

Applicant:

MARLEE SPEEDWAY CHUY S LLC

Description:

FULL INSPECTION

Outstanding Inspections

Case Number: T07FR02444
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02444
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
03/06/2008 VIOL - PRECAUTION AGAINST FIRE MWAINWRI Approved 2006 IFC 315.2 REMOVE ALL COMOBUSTIBLES FROM HOT WATER HEATER IN CLOSET.
03/06/2008 VIOL - COMPRESSED GASES MWAINWRI Approved 2006 IFC 3004.1 CHAIN CO2 BOTTLES IN KITCHEN AREA TO KEEP SECURED.
03/06/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 HAVE FIRE EXTINGUISHER BY EAST EXIT DOOR TESTED AND TAGGED
03/06/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.6.1 REPLACE MISSING FILTERS UNDER HOOD. ONE UNDER BBQ THE OTHER UNDER THE GAS BURNERS. MAKE SURE THE FIT IS TIGHT. REPLACE ANY BENT FILTERS WHICH DO NOT FIT PROPERLY.
03/06/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.4 PLUG ELECTRICAL CORD BY ARCADE MACHINES DIRECTLY INTO RECEPTICLE. USE A FUSED POWER STRIP FOR NEON LIGHTS ABOVE FRONT COUNTER
03/06/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8 REMOVE DBL KEYED LOCK AT EAST EXIT DOOR AND REPLACE WITH A THUMB TURN. AND THE TWO N EXIT DOORS.
03/06/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 REPAIR EXIT LILGHT OAT REAR EXIT DOOR IN KITCHEN
03/06/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT BY ARCADE MACHINE.