Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/29/2007

Applicant:

MC DONALDS REAL ESTATE COMPANY

Description:

Hood suppression System inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02439
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/29/2007 VIOL - FIRE PROTECTION SYSTEMS JBEZEL Approved The Tucson Fire Department has conducted a hood suppression system inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Manual pull stations are too close to cooking appliances. TFC REF: 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximumof 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. REQUIRED CORRECTION: Have required manual pull stations installed per code. ___2. PROBLEM: Service records not produced on premises. TFC REF: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. REQUIRED CORRECTION: All inspection, repair and maintenance records shall be kept on the premises and produced upon request. ___3. PROBLEM: Caps missing from hood nozzles. These caps are necessary to keep nozzles from becoming plugged by grease build up. TFC REF: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. NFPA REF: 17A, 4.3.1.5: All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors, moisture or other foreign materials into the piping. REQUIRED CORRECTION: Nozzle tips on suppression hood shall be free of obstructions and shall be capped. Property Representative Signature:_________________________ Fire Inspector Signature:_________________________(791-4502). Reinspection Date: ___/___/___ _X__Approved ___Not Approved