Case: T07FR02434
Case Details
Entered Date:
11/29/2007
Applicant:
STINGER SALLY JO & STINGER ANGELA JT/RS
Description:
Door is locked, requiring a key code in order to exit building.
Outstanding Inspections
Case Number: T07FR02434
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2007 | INSP - FULL | RESSLING | Correction Required | Door is reportedly locked and requires a special key-code in order to exit. Per Capt JD Leach, "obviously a special knowledge violation." |
| 11/29/2007 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1008.1.8 DOOR OPERATIONS. 1) REMOVE ELECTRONIC KEYPAD LOCK FROM FRONT DOOR. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02434
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | COMPL - INITIAL INSPECTION | JVINCENT | Approved | ORDERED TO REMOVE ELECTRONIC KEYPAD LOCK FROM FRONT DOOR. DOUBLE KEYED DEADBOLT APPROVED WITH THE FOLLOWING CONDITIONS: SPRINKLERED ILLUMINATED EXIT SIGNS EMERGENCY LIGHTING STAFF TO CARRY KEYS AT ALL TIMES LOCK BOX ALL REQUIREMENTS MET. APPROVED. |