Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/29/2007

Applicant:

JONATHAN S RESTAURANT LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02432
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
11/29/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 HAVE K BOTTLE TESTED AND TAGGED AND MOUNTED IN KITCHEN IN AN ACCESSIBLE AREA.
11/29/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8 REMOVE DOUBLE KEYED LOCK ON KITCHEN EXIT DOOR AND REPLACE WITH A THUMB TURN
11/29/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT IN ENTRY
11/29/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.3.5 REMOVE CHAIN FROM GATE IN PATIO AS IT SI USED AS AN EXIT AND INSTALL A PAN IC BAR OR LEVER FOR EXITING
11/29/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.5 REMOVE EXTENSION CORD IN KITCHEN BY MICROWAVE
11/29/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 603.4 REMOVE PORTABLE PROPANE HEATERS FROM ENCLOSED PATIO
11/29/2007 VIOL - FIRE SERVICE FEATURES MWAINWRI Approved 2006 IFC 505.1 INSTALL ADDRESS NUMBERS ON YOUR BUSINESS ACCORDING TO PIMA COUNTY REQUIREMENTS.
03/06/2008 INSP - FULL MWAINWRI Approved