Case: T07FR02423
Case Details
Entered Date:
11/27/2007
Applicant:
HILLER JOHN L & DONNA F REVOC TR
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02423
Case Description: INSPECTION
Total Completed Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2007 | VIOL - FLAMMABLE LIQUIDS | DRAMIREZ | Approved | TFC 3404.2.3 Containers containing flammable and hazardous materials shall be labled. |
| 10/09/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 912.3 Cars parked in front of FDC's |
| 10/09/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 906.6 Extinguisher located on east wall north of exit is not readily accessable. |
| 10/09/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 901.6.2 Shall provide records of inspections and maint. |
| 10/09/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 901.6 Inspection for sprinkler system past due. |
| 10/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Open junction boxes and open wire-splicing shall be prohibited.Approved covers shall be provided for all switch and electrical outlet boxes. |
| 10/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC605.4 Unfussed multiplug adaptors shall be prohibited. |
| 10/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | Extension cords shall not be a substitute for permanent wiring. Ext. cords shall not: Be affixed to structures Extend through walls, ceilings, floors or floor coverings. Shall be maintained in good working order without splices, deterioration or damage. |
| 10/09/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1028.4 Burnt out exit signs. |
| 10/09/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1028.2 Access to SW exit door is obstructed. Access and discharge is obstructed to Norh exit. |
| 10/09/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8.3 Post sign adjacent to main exit reading " THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" |
| 10/09/2007 | INSP - FULL | DRAMIREZ | Approved |