Description:

Full inspection (Fraternity)

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02355
Case Description: INSPECTION
Total Completed Inspections - 9
End Date Description Inspector Results Comments
11/19/2007 VIOL - MEANS OF EGRESS BCORRALE Approved ____Emergency lighting out of service.( Lobby and T.V. room) 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. ***Repair lighting.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved Smoke detectors need battery test. 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. ***Test, and submit log to T.F.D.
11/19/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved ____Electrical cover plates missing.(2 in dining room, 1 in chapter room.) ____Cable coaxial connection cover plates loose.(2 in Dining room) 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. ***Install, reset all missing covers.
11/19/2007 VIOL - FIRE RESIST.RATED CONST BCORRALE Approved ____Sprinkler escutcheon plate is not seated correctly. (dining room) 703.1 Maintenance The required fire-resistance-rated construction shall be maintained. Such elements shall be repaired, restored, or replaced when damaged, altered, breached, or penetrated. ***Reseat plate.
11/19/2007 VIOL - FIRE SERVICE FEATURES BCORRALE Approved ____Sign is needed to denote location of Fire Department Connections (FDC's). 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters "FDC" at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. ***Install approved sign.
11/19/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved ____Paint buckets in computer closet. 315.2.3 Equipment rooms. Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. ***Remove paint buckets from computer closet.
11/19/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved ____Lint buildup in laundry room. 316.2 Clothes dryers. Clothes dryers shall be frequently cleaned to maintain the lint trap and mechanical and heating components free from excessive accumulations of lint. ***Clean ALL lint from laundry room.
11/19/2007 INSP - FULL BCORRALE Approved On 11-14-07, a fire prevention inspection was conducted at the Kappa Sigma house, 1423 E. 1st St. Please correct the following Tucson Fire Code violations. All references are from the 2006 International Fire Code, with modifications.
01/30/2008 INSP - REINSPECTION BCORRALE Approved ALL O.K., COMPLIANT.