Case: T07FR02318
Case Details
Entered Date:
11/15/2007
Applicant:
TMC FOUNDATION
Description:
Fire Inspection
Outstanding Inspections
Case Number: T07FR02318
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | TFC 605.3 WORKING SPACE AND CLEARANCE. 1) REMOVE ITEMS FROM FRONT OF ELECTRICAL PANEL. SE NURSING STATION. |
| 11/15/2007 | VIOL - FIRE RESIST.RATED CONST | JVINCENT | Violation | TFC 703.1 MAINTENANCE. 1) INSTALL MISSING CEILING TILE IN STORAGE ROOM. SE STORAGE ROOM. |
| 11/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 906.2 GENERAL REQUIREMENTS 1) MOUNT FIRE EXTINGUISHER IN AN UNOBSTRUCTED OR UNOBSCURED AREA. 2) SERVICE AND TAG EXTINGUISHER. |
| 11/15/2007 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1028.3 OBSTRUCTIONS. 1) REMOVE OBSTRUCTIONS FROM NORTH SIDE EGRESS DOOR. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02318
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | INSP - FULL | JVINCENT | Approved | SIP REFUSED AND FULL FIRE INSPECTION REQUESTED BY BUSINESS. |