Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/14/2007

Applicant:

WONG FAMILY LTD PARTNERSHIP

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T07FR02296
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
12/14/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 REPLACE MISSING ELEC COVER PLATE ONOUTLET IN NORTH STOCK ROOM INSTALL COVER PLATES ON ALL JUNCTION BOXES IN CEILILNG REPAIR BARE WIRES HANGING DOWN FROM CEILING
12/14/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 HAVE BOTH FIRE EXTINGUISHERS IN KITCHEN SERVICED AND TAGGED. HAVE FIRE EXTINGUISHER IN PANTRY SERVICED AND TAGGED HAVE SPRINKLER SYSTEM SERVICED AND TAGGED.
12/14/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.5 PURCHASE A K BOTTLE EXTINGUISHER FOR KITCHEN
12/14/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.6.3 HAVE THE ENTIRE HOOD SYSTEM CLEANED FROM ROOF DOWN TO FILTERS BY NOV 19TH 2007
12/14/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation HAVE HOOD SYSTEM INSPECTED AND PUT BACK IN SERVICE. COMPLETE THIS INSPECTON BY 11/16/07.
12/14/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8 REMOVE THE DBL KEYED LOCK ON THE INTERIOR MAIN ENTRY DOOR AND REPLACE WITH A THUMB TURN. REMOVE DBL KEYED LOCK ON DOOR IN LAUNDRY ROOM AND REPLACE WITH A THUMB TURN. REMOVE DBL KEYED LOCK ON EAST EXIT DOOR IN KITCHEN BY PANTRY AND REPLACE WITH A THUMB TURN.
12/14/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8.3 PLACE A SIGN ON THE FRONT ENTRANCE DOOR STATING "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS"
12/14/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR EMERGENCY LILGHT IN KICHEN

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02296
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/27/2009 INSP - FULL MWAINWRI Approved