Case: T07FR02296
Case Details
Entered Date:
11/14/2007
Applicant:
WONG FAMILY LTD PARTNERSHIP
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T07FR02296
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2007 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 REPLACE MISSING ELEC COVER PLATE ONOUTLET IN NORTH STOCK ROOM INSTALL COVER PLATES ON ALL JUNCTION BOXES IN CEILILNG REPAIR BARE WIRES HANGING DOWN FROM CEILING |
| 12/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 HAVE BOTH FIRE EXTINGUISHERS IN KITCHEN SERVICED AND TAGGED. HAVE FIRE EXTINGUISHER IN PANTRY SERVICED AND TAGGED HAVE SPRINKLER SYSTEM SERVICED AND TAGGED. |
| 12/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 904.11.5 PURCHASE A K BOTTLE EXTINGUISHER FOR KITCHEN |
| 12/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 904.11.6.3 HAVE THE ENTIRE HOOD SYSTEM CLEANED FROM ROOF DOWN TO FILTERS BY NOV 19TH 2007 |
| 12/14/2007 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | HAVE HOOD SYSTEM INSPECTED AND PUT BACK IN SERVICE. COMPLETE THIS INSPECTON BY 11/16/07. |
| 12/14/2007 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1008.1.8 REMOVE THE DBL KEYED LOCK ON THE INTERIOR MAIN ENTRY DOOR AND REPLACE WITH A THUMB TURN. REMOVE DBL KEYED LOCK ON DOOR IN LAUNDRY ROOM AND REPLACE WITH A THUMB TURN. REMOVE DBL KEYED LOCK ON EAST EXIT DOOR IN KITCHEN BY PANTRY AND REPLACE WITH A THUMB TURN. |
| 12/14/2007 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1008.1.8.3 PLACE A SIGN ON THE FRONT ENTRANCE DOOR STATING "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" |
| 12/14/2007 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR EMERGENCY LILGHT IN KICHEN |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02296
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2009 | INSP - FULL | MWAINWRI | Approved |