Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/09/2007

Applicant:

GEE PROPERTIES-2 LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR02268
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
11/09/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 The electrical outlet located in the kitchen by the cooking equipment shall be properly anchored to the wall.
11/09/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Properly align hood extinguishing system nozzles over cooking equipment.
11/09/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease accumulation from the hood system and cooking equipment.
11/09/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Mount the class K rated fire extinguisher located in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02268
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/26/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.