Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/07/2007

Applicant:

WEST MAIN STREET LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02259
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
11/07/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 901.7 SERVICE AND TAG ALL FIRE EXTINGUISHERS AND HAND ON BRACKETS IN ACESSIBLE AREAS WHICH NEED TO BE MOUNTED
11/07/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2006 IFC 703.1 REPAIR HOLE IN CEILING IN ISLE 10
11/07/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.5 REMOVE EXTENSION CORD IN COMPUTER ROOM REMOVE EXTENSION CORD GOING THROUGH WALL IN STOCK ROOM AREA BY SERVICE DEPT DOOR
11/07/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.1 INSTALL BLANKS IN ELECTRICAL PANEL BY STORAGE ROOM REPLACE BROKEN OUTLET IN SEPARATE WAREHOUE W SIDE
11/07/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8 REMOVE DBL KEYED LOCK ONEXIT DOOR BY BATHROOM IN MAIN LOBBY. REPLACE WITH A THUMB TURN
01/10/2008 INSP - FULL MWAINWRI Approved