Case: T07FR02232
Case Details
Entered Date:
10/30/2007
Applicant:
DND NEFFSON CO
Description:
Full Inspection.
Outstanding Inspections
Case Number: T07FR02232
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from obstructing the electrical service equipment located in the back room by the door. |
10/30/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Replace all painted sprinkler heads. #2.Repair the sprinkler head located in the office. NOTE:It needs to be pushed down through the ceiling. |
10/30/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 The emergency lighting unit located in the back room by the pizza boxes shall be repaired. |
10/30/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Secure all compressed gas cylinders with an approved restraint device. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02232
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |