Case: T07FR02230
Case Details
Entered Date:
10/30/2007
Applicant:
DND NEFFSON CO
Description:
Full inspection.
Outstanding Inspections
Case Number: T07FR02230
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag the kitchen hood extinguishing system. #2.Service and tag the class K portable fire extinguisher. #3.Remove lint accumulation from all automatic sprinkler heads. |
10/30/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood system and cooking equipment. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02230
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |