Case: T07FR02228
Case Details
Entered Date:
10/30/2007
Applicant:
DND NEFFSON CO
Description:
Full Inspection.
Outstanding Inspections
Case Number: T07FR02228
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the kitchen hood extinguishing system. |
10/30/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.5 A class B:C rated fire extinguisher shall be within 30 foot travel distance of cooking equipment. |
10/30/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 The exit sign located in the back room shall be illuminated. |
10/30/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 The emergency lighting unit located by the exit sign shall be repaired. |
10/30/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Secure all compressed gas cylinders with an approved restraint device. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02228
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2007 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |