Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T07FR02224
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
10/30/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.1 REMOVE THE BRASS LOCKS ON BREAKERS INYOU ELECTRICAL PANELS. THESE LOCKS DEFEAT THE PURPOSE OF THE BREAKER TRIPPING IF THERE IS AN OVER LOAD.
10/30/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8.5 REMOVE THUMB TURN ON KITCHEN EXIT DOOR SO THERE IS ONLY ONE OPERATION TO OPEN THE DOOR. THE PANIC BAR CAN BE THE ONLY LOCKING MECHANISM.
10/30/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 HAVE EMERGENCY LIGHTS CHECKED TO SEE IF THEY OPERATE WHEN THE POWER IS OFF. HAVE AN ELECTRICIAN DEMONSTRATE HOW TO PERFORM THIS TEST.
10/30/2007 INSP - FULL MWAINWRI Approved 2006 IFC 912.4 INSTALL SIGN ON MENS BATHROOM DOOR STATING "RISER ROOM" THEN INSIDE THE BATHROOM INSTALL SIGN STATING "RISER ROOM" ON THE RISER DOOR.
10/30/2007 INSP - FULL MWAINWRI Approved 2006 IFC 901.6 HAVE SPRINKLER SYSTEM TESTED AND TAGGED.