Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR02205
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag the hood extinguishing system. #2.Service and tag all portable fire extinguishers. #3.Properly align hood extinguishing system nozzles over cooking equipment.
10/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease build-up from the hood system and cooking equipment. Provide documentation of such cleanings.
10/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8 Remove the thumb-turn lock from the egress door in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02205
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/08/2007 INSP - FULL JBURGE Approved All Noted Tucson Fire Code violations were corrected.