Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02073
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
10/15/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2006 IFC 703.1 REPLACE MISSING CEILING TILES AROUND ICE MACHINE
10/15/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.6.1 REPLACE MISSING HOOD FILTER
10/15/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.6.3 HAVE DUCTS CLEANED BEHIND FILTERS ALL THE WAY TO THE ROOF.
10/15/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 1) HAVE K BOTTLE INSPECTED AND TAGGED. 2) HAVE FIRE EXTINGUISHER SERVICED AND TAGGED BY ICE M 3) HAVE HOOD SYSTEM INSPECTED AND TAGGED
10/15/2007 VIOL - FIRE SERVICE FEATURES MWAINWRI Approved 2006 IFC 505.1 DISPLAY ADDRESS NUMBERS WHERE THEY ARE VISABLE FROM SPEEDWAY ACCORDING TO PIMA COUNTY ADDRESSING CODE
03/06/2008 INSP - FULL MWAINWRI Approved