Description:

full fire prevention inspection

Outstanding Inspections

Case Number: T07FR02072
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
End Date Description Inspector Results Comments
10/25/2007 VIOL - PRECAUTION AGAINST FIRE JVINCENT Violation TFC 315.2.1 1) Provide 18" clearance below sprinklers in kitchen area.
10/25/2007 VIOL - EMERGENCY PLAN/PREPARE JVINCENT Violation TFC 408.11.2 1) Provide business name and/or address on exterior of rear exit doors.
10/25/2007 VIOL - FIRE SERVICE FEATURES JVINCENT Violation TFC 510.1 1) Post a sign indicating the location of FDC's.
10/25/2007 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Violation TFC 605.3 1) Provide clearance for main electrical panel.
10/25/2007 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Violation TFC 605.6 1) Install blanks in open spaces within main electrical panel.
10/25/2007 VIOL - FIRE RESIST.RATED CONST JVINCENT Violation TFC 703.1 1) Install missing ceiling tiles in kitchen.
10/25/2007 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 904.11.6.3 1) Clean and remove all grease accumulation from hood systems and cooking equipment.
10/25/2007 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 901.6 1) Service sprinkler system. 2) Clean all sprinkler heads in kitchen area.
10/25/2007 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 901.6.1 1) Position discharge nozzles for proper coverage over cooking equipment.
10/25/2007 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 904.11.5 1) Provide and mount a class K portable extinguisher in kitchen area.
10/25/2007 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 904.11.6.4 1) Service hood systems.
10/26/2007 INSP - FULL JVINCENT Correction Required Please correct the following Tucson Fire Code violations:
10/26/2007 VIOL - MEANS OF EGRESS JVINCENT Violation TFC 1008.1.8 1) remove key operated lock from NE door, kitchen door, and kitchen gate. replace with thumb turn lock.
10/26/2007 VIOL - MEANS OF EGRESS JVINCENT Violation TFC 1027.3 1) front exit door sign needs illumination. 2) rear exit door sign needs illumination.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02072
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/23/2008 INSP - REINSPECTION JVINCENT Approved ALL VIOLATIONS CORRECTED.