Case: T07FR02072
Case Details
Entered Date:
10/12/2007
Applicant:
NOLA DEVELOPMENT LTD PARTNERSHIP
Description:
full fire prevention inspection
Outstanding Inspections
Case Number: T07FR02072
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2007 | VIOL - PRECAUTION AGAINST FIRE | JVINCENT | Violation | TFC 315.2.1 1) Provide 18" clearance below sprinklers in kitchen area. |
10/25/2007 | VIOL - EMERGENCY PLAN/PREPARE | JVINCENT | Violation | TFC 408.11.2 1) Provide business name and/or address on exterior of rear exit doors. |
10/25/2007 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Violation | TFC 510.1 1) Post a sign indicating the location of FDC's. |
10/25/2007 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | TFC 605.3 1) Provide clearance for main electrical panel. |
10/25/2007 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | TFC 605.6 1) Install blanks in open spaces within main electrical panel. |
10/25/2007 | VIOL - FIRE RESIST.RATED CONST | JVINCENT | Violation | TFC 703.1 1) Install missing ceiling tiles in kitchen. |
10/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 904.11.6.3 1) Clean and remove all grease accumulation from hood systems and cooking equipment. |
10/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 901.6 1) Service sprinkler system. 2) Clean all sprinkler heads in kitchen area. |
10/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 901.6.1 1) Position discharge nozzles for proper coverage over cooking equipment. |
10/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 904.11.5 1) Provide and mount a class K portable extinguisher in kitchen area. |
10/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 904.11.6.4 1) Service hood systems. |
10/26/2007 | INSP - FULL | JVINCENT | Correction Required | Please correct the following Tucson Fire Code violations: |
10/26/2007 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1008.1.8 1) remove key operated lock from NE door, kitchen door, and kitchen gate. replace with thumb turn lock. |
10/26/2007 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1027.3 1) front exit door sign needs illumination. 2) rear exit door sign needs illumination. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02072
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2008 | INSP - REINSPECTION | JVINCENT | Approved | ALL VIOLATIONS CORRECTED. |