Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

10/10/2007

Applicant:

SEA TAB LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR02059
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
10/10/2007 INSP - FULL JBURGE Correction Required Please correct the following Tucson Fire Code violations:
10/10/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace all missing ceiling tiles.
10/10/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease accumulation from both hood systems and cooking equipment.
10/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.2 All exit gates located in the patio shall swing in the direction of egress travel.
10/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 Post a sign stating THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED, on the north exit gate.
10/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Remove the surface bolt from the exit gate on the north side of the patio.
10/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 The east exit gate shall have an illuminated exit sign posted.
10/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Repair the emergency lighting unit located on the inside east exit doorway. NOTE: replace the right bulb.
10/10/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Secure all compressed gas cylinders to a fixed object with one or more restraints. NOTE: Located by the beer walk in.