Case: T07FR01999
Case Details
Entered Date:
10/08/2007
Applicant:
BARKK ENTERPRISES LLC
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01999
Case Description: INSPECTION
Total Completed Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | VIOL - COMBUSTIBLE FIBERS | DRAMIREZ | Approved | TFC 906.2 Portable fire extinguishers shall be maintained and serviced annually. |
| 10/08/2007 | VIOL - HAZARDOUS MATERIALS,GEN | DRAMIREZ | Approved | TFC 2703.4 Shall provide Material Safety Data Sheet (MSDS). |
| 10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.3.1 Door into electrical room shall be marked: ELECTRICAL ROOM. |
| 10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Shall provide cover plate for electrical box in electrical room. |
| 10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4 Unapproved multiplug adaptors shall be prohibited. |
| 10/08/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8 Shall provide sign over main exit door stating: THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED. Shall provide thumb-turn lock for west exit, warehouse area. |
| 10/08/2007 | INSP - FULL | DRAMIREZ | Approved | TFC 107.1 Emergency equipment or devices shall be continuously maintained. 1.) exit sign over main enterance, burnt. 2.) west exit, warehouse, sign is burnt. |