Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/01/2007

Applicant:

SUPER INTERMEDIATECO LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR01922
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
10/01/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 #1.Open space in the electrical service panel's, shall be covered with electrical blanks. #2.Repair the electrical conduit and wiring for the fryer exhaust system located on the roof.
10/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6.1 The fire alarm system shall be serviced and tested.
10/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11 Submit plans for the addition of nozzles to cover the gridle and salamander located on the north side of the kitchen.
10/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 #1.Clean and remove all grease build-up from hood systems and cooking equipment. #2.The fryers shall be maintained in the proper position correctly under the hood system nozzles.
10/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the padlock and hardware from the egress gate located on the west side of the loading dock.
10/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Remove the surface bolt from the egress gate located on the west side of the loading dock.
10/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 #1.Repair the emergency lighting unit located in the men's restroom. #2.Repair the emergency lighting unit located in the women's restroom. #3.Repair the emergency lighting unit located by the south entrance to the lounge.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01922
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/01/2007 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: