Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/28/2007

Applicant:

ECKENRODE PARTNERSHIP

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR01910
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
09/28/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag all portable fire extinguishers.
09/28/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6 #1.The portable fire extinguisher located by the east exit door shall not be obstructed. #2.The portable fire extinguisher located by the west exit door shall not be obstructed.
09/28/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 The portable fire extinguishers located in both offices shall be mounted on a hanger or bracket.
09/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The exit door located in the office shall have: THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED, posed on or above the door.
09/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 #1.The exit sign located in the office shall have emergency back-up power. #2.Repair all the emergency lighting units located on the south wall in the warehouse. #3.The exit sign located above the west exit door in the shop shall have emergency back-up power.
09/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 The east exit door located in the warehouse shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01910
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/27/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.