Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/28/2007

Applicant:

AREC 12 LLC

Description:

Full inspection done Sept. 26th, 2007; U-Haul , "S1" occupancy; 575-5376 Michael Kotch- manager; Assisted by FF Noah Brown.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01907
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
09/28/2007 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Housekeeping: IFC2006 [with modifications] 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate. ______ Remove storage from around water heater. in buildings or structures or upon premises. Re-inspection date scheduled on or after Oct. 19, 2007. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain
09/28/2007 VIOL - MEANS OF EGRESS BCOBB Approved Front Door IFC2006 (with modifications) / 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. ______ Place sign over front door.
09/28/2007 VIOL - FIRE SERVICE FEATURES BCOBB Approved Door removed from service illegally: IFC 2006 [with modifications]/ 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. ______ Provide documentation that door was decommisioned for use by DSD.
09/28/2007 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Extension cords: IFC2006 [With modifications]/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Remove all or replace with approved power strip. [many in garage used for door openers, microwave, etc]
09/28/2007 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Assorted electrical hazards: TFC2006/ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ All timer boxes shall be locked to prevent shock. ______ Electric box side needs conduit re-attached. [upstairs] ______ Same box needs a "blank" inside. ______ Electric conduit in garage pulled out of receptacle box. ______ Replace burnt electrical outlet [downstairs noth wing] ______ Steele cap for hole in electric box [downstairs] ______ Secure outlet on wall [south wing] ______ Cap wires in timer bos [garage] ______ Receptacle broke -replace [garage]
09/28/2007 VIOL - MEANS OF EGRESS BCOBB Approved Exit signs not lit: IFC2006 [with modifications / 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit signs.
09/28/2007 VIOL - MEANS OF EGRESS BCOBB Approved Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. [2 upstairs,2 downstairs. Replace broken ones.]
09/28/2007 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code [IFC 2006 with modifications] violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ______ C of O on site.