Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/24/2007

Applicant:

ECKENRODE DAVID

Description:

Full fire Inspection.

Outstanding Inspections

Case Number: T07FR01867
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
09/24/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Repair all holes in the drywall located in the shop.
09/24/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag all portable fire extinguishers.
09/24/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 All portable fire extinguishers shall be mounted.
09/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 #1.The northeast exit door in the shop shall not be obstructed. #2.The southwest exit door in the shop shall not be obstructed.
09/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 #1.Repair the emergency lighting unit located on the west wall in the shop. #2.All exit signs shall have emergency back-up power.
09/24/2007 VIOL - HAZARDOUS MATERIALS,GEN JBURGE Correction Required TFC 2703.5.1 Label the waste oil containers located by the west wall in the shop.
09/24/2007 VIOL - FLAMMABLE LIQUIDS JBURGE Correction Required TFC 3404.3.2 Flamable liquids and paint shall be stored in an approved flammable liquid storage cabinet. A re-inspection is scheduled for 10-8-07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01867
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/19/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 10-17-07.