Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01848
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
04/10/2008 VIOL - FIRE SERVICE FEATURES MWAINWRI Approved 2006 IFC 506.1 INSTALL SWITCH IN KNOX BOX FOR GATE ENTRY.
04/10/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 912.4 MARK THE MECHANICAL ROOM 4 WITH A SIGN STATING RISER ROOM.
04/10/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.3.1 MARK THE MECHANICAL ROOM 1 WITH A SIGN STATING ELECTRICAL ROOM IN 1 INCH LETTERS
04/10/2008 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 REPAIR THE EMERGENCY LIGHTS AT THE FOLLOWING LOCATIONS 2010,2016,2033,2022, 3 EMERG LIGHTS IN STAIR WELL BY SOUTH DOOR EXIT ON 1ST FLOOR MIDDLE EMERG LIGHT IN HALL GOING NORTH BY MECH ROOM2 EMERG LIGHT AT END OF HALL BY NORTH EXIT DOOR MECH ROOM1 EMRG LIGHT AT END OF HALL BY NORTH EXIT DIIR MECH RM 2 EMERG LIGHT IN STIRWELL BY MECH ROOM 1 EMRG LIGHT BY 2081 EMERG LIGHT IN STAIRWELL BY MECH ROOM 4 EMERGENCY LIGHT BY 3002,3042-3055,3020,3032,3074,3210,3088,3090,3105,3096,3079,3201,3178-3193,3160-3177,3136-3159,3120-3135,2055
04/10/2008 INSP - FULL MWAINWRI Approved