Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/19/2007

Applicant:

PRESSON MIDWAY LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01819
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
12/19/2007 INSP - FULL MWAINWRI Approved
12/19/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.5 PURCHASE A CLASS K EXITINGUISHER AND MOUNT WITHIN 30 FEET OF HOOD.
12/19/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 TEST HOOD SYSTEM TEST EXTINGUISHERS IN KITCHEN ALIGN HEADS FOR PROPER PLACEMENT OVER EQUIPMENT
12/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1028.2 CLEAR EXIT DOOR OF STORAGE RACKS IN BACK ROOM AND REPAIR DOOR SO THUMB TURN WILL WORK EASILY.
12/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 EMER LIGHT ON WEST WALL IN DINING ROOM EMER LIGHT ON EAST WALL INFRONT EMER LIGHT IN MIDDLE OF DINING AREA EAST WALL EMER LIGHT AT SE EXIT DOOR EMER LIGHT IN KITCHEN
12/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 2 EXIT SIGNS AT FRONT ENTRANCE EXIT SIGN AT SE EXIT DOOR EXIT SIGN IN BACK STORAGE AREA EXIT SIGN AT EXIT DOOR IN KITCHEN