Case: T07FR01813
Case Details
Entered Date:
09/18/2007
Applicant:
SYDCO SIXTEENTH STREET LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T07FR01813
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | INSP - FULL | BCORRALE | Continued | On 9-18-07, a fire prevention inspection was conducted at 576 E. 16th St. Please correct the following Tucson Fire Code violations. All references are from the 2006 International Fire Code, with modifications. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01813
Case Description: INSPECTION
Total Completed Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | VIOL - FIRE SERVICE FEATURES | BCORRALE | Approved | Unable to see sprinkler riser due to storage, sign is needed to identify location of riser. 2006 IFC 510.1 *** Install sign. |
| 09/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | Fire extinguisher needs to be re-mounted in break room. 2006 IFC 906.7 ***Re-install hanger bracket. |
| 09/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Approved | Extension cords used to power permanent equipment. -Dispatch area. -throughout office area. 2006 IFC 605.5 ***Replace ALL extension cords in building with approved electrical supply, with overcurrent protection, and circuit breakers. |
| 01/25/2008 | INSP - REINSPECTION | BCORRALE | Approved | all O.K. |