Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/10/2007

Applicant:

WALKER TUCSON PROPERTY LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T07FR01767
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
09/10/2007 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 304.1.1/304.1.2 Combustible waste and vegitation at south side of building shall be removed.
09/10/2007 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in warehouse shall be maintained 18 inches below sprinkler heads.
09/10/2007 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Junction box at warehouse on west wall shall have a cover.
09/10/2007 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Ceiling tiles in warehouse and storage room shall be repaired.
09/10/2007 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Hole in wall at east side of warehouse shall be repaired.
09/10/2007 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 Portable fire extinguishers near printing machines shall be mounted on brackets.
09/10/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.3 Exit signs throughout need repair.
09/10/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 Emergency lights at east and south exits shall be repaired.
09/10/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.8 Panic hardware installed with deadbolt lock at breakroom west exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01767
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/08/2007 INSP - FULL TKNAPP Approved